TYPICAL APPLICATIONS (wiring diagrams)

Figure-1 through Figure-3 illustrate typical wiring diagrams for spring return floating
actuators. See Table-1 for model selection.

MA4X-7153

MA4X-7073

MA4X-7153-502

MA4X-7073-502

2

1

1 Provide overload protection and disconnect as required.

2 Actuators mounted on separate shafts may be wired in

parallel. All actuator black wires are connected to the
transformer common and all red wires are connected to
the hot lead. Power consumption must be observed.

3 For end position indication, interlock control, fan startup,

etc., MA4X-715X-502, and MA4X-707X-502 models
incorporate two built-in auxiliary switches.

24 Vac Transformer

or 22-30 Vdc

Blk

Red

Com

Hot (+DC)

Line

Volts

Grn/Yel

SPST Control Contact

2

1

MA4X-7150

MA4X-7151

MA4X-7070

MA4X-7071

MA4X-7150-502

MA4X-7151-502

MA4X-7070-502

MA4X-7071-502

Wire No. 1

Wire No. 2

Com

Hot

L1 N

L2 H

120 Vac or

230 Vac

Grn/Yel

Org/Wht

Vio/Wht

Yel/Wht

NC

NO

3

Org

Vio

Yel

NC

NO

Com

Com

Aux Switch 1

Aux Switch 2

25 to 85°

Adjustable

5° Fixed

Aux Switches

MA4X-7XXX-502

Optional Auxiliary

Switches

120 Vac

White

Black

230 Vac

Blue

Brown

Voltage

Wire 1

Wire 2

Figure-1 Typical Wiring Diagram for 24 Vac Basic and Double Auxiliary Switch Models.

MX40-707X-502 and MX40-715X-502 units manufactured prior to the date code 0141
(October 6, 2001) used the following color coding for the auxiliary switches:

Auxiliary Switch 1

Orange:

Fixed auxiliary switch common (com)

Yellow:

Fixed auxiliary switch normally closed (NC)

Violet:

Fixed auxiliary switch normally open (NO)

Auxiliary Switch 2

Orange/white:

Adjustable auxiliary switch common (com)

Violet/white:

Adjustable auxiliary switch normally closed (NC)

Yellow/white:

Adjustable auxiliary switch normally open (NO)

The label information on these units is incorrect. If replacing these units, the auxiliary switch
operation of the replacement actuator will be per the product label.