Installing and Configuring the Module

20

840 USE 115 00 Version 1.0

2.3

Changing the Default Configuration

If any of the following conditions apply, you should stop the controller, then install
the module, then change the default configuration before starting the controller
again:

z

The module will be communicating on an open Ethernet network.

z

The module’s IP address is already in use.

z

The network uses IEEE 802.3 framing.

z

You must specify a default Ethernet gateway and subnet mask.

If you change the configuration after installing the module, you must reset the
module for your changes to take effect.

You may configure the module using Modsoft or Concept.

2.4

Configuring the Module with Modsoft

From the Modsoft Configuration Overview screen, select the Cfg Ext pulldown
menu.

Be sure that you have specified sufficient memory resources for the Ethernet
configuration extension in the Cfg. Extension Size field. The first Ethernet module
configured requires 20 words. Each additional module requires an additional 16
words.

From the options, select TCP/IP Setup. You will reach the Ethernet configuration
extension screen.