Installing and Configuring the Module

840 USE 115 00 Version 1.0

23

2.4.6

Configuring More Than One Ethernet Module

You may configure from two to six Ethernet modules in a single controller,
depending on the model. A 140 CPU 113 or 213 will accept a total of two network
option modules, including NOE, NOM, NOP, CRP 811and other modules. A 140
CPU 424, 434 or 534 will accept six.

The first Ethernet web embedded server module configured requires 20 words of
memory. Each additional module requires an additional 16 words of memory.

The modules may be placed in any slot in the backplane. They do not have to be
placed next to each other.

To configure the modules, simply page down to an unused configuration extension
screen. Enter the backplane slot number to activate the screen.