Example of internal circuit and wiring, Output specification – Sierra Monitor Corporation PF2A7H User Manual

Page 6

Advertising
background image

9

8

OUT1

Analog Output

Load

Load

24VDC

1

4

2

3

Brown

Black

White

Blue

Main Circuit

Analog Output

OUT1

Load

Load

Brown

Black

Blue

White

1

4

2

3

24VDC

Main Circuit

Connector pin number

Min. measured flow Max. measured flow

1

5

Analog Output [

]

4

20

Analog Output [

]

Instantaneous flow [

/ min ]

Output Specification

When the Lead wire with connector provided by SMC corporation
is used the color of wire (Brown, white, Black, Blue) shown on
circuit diagram will be applied.

28,

29

NPN open collector 1 output + Analog output
Max. 30V, 80mA Internal voltage drop : 1V or less

68,

69

PNP open collector 1 output + Analog output

Max. 80mA Internal voltage drop : 1.5V or less

Example of Internal Circuit and Wiring

4

3

1

2

Key

Turn off power before connecting or disconnecting the connector.
To insert the connector, push the connector socket of the lead
wire to the key part of the switch connector after aligning them
to each other and secure the connector with the lock nut.
To disconnect the connector, unlock the connector lock nut and
pull out the connector straight.
Install the lead wire separately from the route for power cable
or high-voltage cable. Otherwise, malfunction may potentially
result due to noise.

PF2A7

H-

-28/68

Output 1 to 5V

PF2A7

H-

-29/69

Output 4 to 20mA

Pin No.

Pin name

1

DC

(

+

)

2

Analog Output

3

DC

(

-

)

4

OUT1

Model No.

Max. measured flow

( /min)

PF2A703H

150

PF2A706H

300

PF2A712H

600

Min. measured flow

( /min)

3000

6000

12000

Advertising