Chapter 3: Main Menu and SubMenus

Liebert RCM8

27

Display SS Alarm
Block

The Display SS Alarm Block option from the Main Menu sends
RCM8 information to a SiteScan alarm block. Alarm
information on up to 4 RCM8 units can be displayed by the
SiteScan.

To display the SiteScan alarm block:

1. From the Main Menu, press A to display the SiteScan alarm

block:

00 00 00 00 00 00 00 01 00 00 00 00 00 00 00 00

00 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00

This is a view-only screen. The first eight sets of 00 in the
top row indicate the eight alarm points of RCM8 unit 1, and
so forth for 32 alarm points on four RCM8 units. The
example above shows an alarm on contact point number 8
on the first RCM8 unit and contact point number 2 on the
third RCM8 unit.

2. When you are finished viewing the information, press Esc to

return to the Main Menu.

Set New Password

The Set New Password option lets you assign a security
password protecting the RCM8 setup menu from unauthorized
changes.

To set a new password:

1. From the Main Menu, press P to access the new password

setup screen.

2. Type the desired new password then press Enter.

The factory-set password is
“RCM8.”

3. At the next prompt, retype the password exactly as you

entered it in step 2, then press Enter to confirm the
password. The new password is saved automatically.

4. Press Esc to exit the password setup screen and return to the

Main Menu.

Exit

The Exit option returns the system to the initial prompts for
Main Menu, Status, or Alarms.