Chapter 3: Main Menu and SubMenus

Liebert RCM8

23

Set Modem Phone Number 2 (3)

Enter a phone number for another receiving modem (if
applicable). Press Enter to return to the Modem Setup menu.

Modem Phone Number 2 is not
a leased-line option.

Using an Alpha-Numeric Pager
When using an alpha-numeric pager, you must enter the
letter "A" before the pager access code phone number.
Refer to the sample screen on page 17 of this manual.
Note: most alpha-numeric paging services do not yet
support 2400 baud modem connections: use 1200 baud.

Using a Numeric Pager
When using a numeric page, an example of the pager
number that you enter is:

Phone Number 1 = 9,5551212,,,,,911##

Each comma forces the mode to pause for two seconds.
The 911 is the user-arranged “code” that identifies the
page as being from the RCM8. The ## signify the end of
the pager number and alarm code.
(See Appendix A on Page A-1 for additional
modem/pager characters.)

When using numeric pagers, you will have to experiment
with the number of commas that you need to enter in
order to get the correct delay before the message is sent.

The Set Pager ID field is left blank when using numeric
pagers.

Set Modem Baud Rate (4)

Enter 1 for 1200 or 2 for 2400. Press Enter to return to the
Modem Setup menu.

Set Dial Prefix (5)

Press 5 if you need to change the dial prefix. From the
factory, the Dial Prefix is entered as ATE1X4DT. Do not
change this dial prefix unless you are thoroughly familiar
with the Hayes command set. Press Esc to return to the
Modem Setup menu.

Set Redial Tries (6)

Enter a number (0-99) representing the number of times the
RCM8 will attempt to redial a phone number should the first
attempt fail. Press Enter to return to the Modem Setup
menu.