Installation – Lennox Hearth L20 BF-2 User Manual

Page 9

Advertising
background image

INSTALLATION -

MODEL L20 DVF-2 ONLY

PAGE 9

Direct Vent Retrofit Of Existing Chimney System - An existing Class-A (wood-burning) Metal Chimney or Masonry Chimney can be
converted to a direct vent system. Use one of the following chimney conversion kits listed below. Have the existing chimney system
inspected by a professional prior to the conversion. If using Simpson Dura-Vent brand liner kit, see “IMPORTANT” note at the top of
page 8.
The chimney conversion should not be applied to the portion of the vent system that is in the room of the appliance. Use only
Co-Axial direct vent pipe (4” inner pipe, 6 5/8” outer pipe as listed on page 8) from the appliance to the retro-connector into converted
flue system. Adhere to all specifications shown on pages 6 and 7 regarding clearances to combustibles, vertical and horizontal vent
length minimums and maximums, etc. Read all instructions in this manual and provided by vent manufacturer with kit carefully before
starting the installation. Failure to follow the instructions may create a fire or other safety hazard, and will void the warranty.

Model #

Brand: SECURITY / Description

Model #

Brand: SIMPSON DURA-VENT / Description

SV4MCK

Masonry Chimney Conversion Kit –Vertical term. Cap,
cap adapter, masonry cover, black adapter (to flex), 2
gear clamps

934

Masonry Chimney Conversion Kit

SV4CCK1

Factory Built Chimney Conversion Kit – for 6” I.D., 1”
insulation.

931

Factory Built Chimney Conversion Kit A – for 6”
I.D.; Only compatible w/specific brands – Contact
Vent Manufacturer

SV4CCK2

Factory Built Chimney Conversion Kit – for 7” I.D., 1”
insulation; 8” I.D., 1” insulation; 6” I.D., 2” insulation.

932

Factory Built Chimney Conversion Kit B – for 6”, 7”
& 8” I.D.; Only compatible w/specific brands –
Contact Vent Manufacturer

SV4CCK3

Factory Built Chimney Conversion Kit – for 10” I.D., 1”
insulation; 7” I.D., 2” insulation; 8” I.D., 2” insulation.

933

Factory Built Chimney Conversion Kit C – for 7” &
8” I.D.; Only compatible w/specific brands – Con-
tact Vent Manufacturer


MODELS L20 BF-2 AND L20 DVF-2
VERTICAL VENT TERMINATION REQUIREMENTS
These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes,
these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and -
B149.2 in Canada.


Terminate multiple vent terminations according to the installation codes listed above.


Terminate single vent caps relative to building components according to the following chart & illustration. The vent/air intake termina-
tion clearances above the high side of an angled roof is as shown in the following chart:













Venting terminals shall not be recessed into a wall or siding.

Ref. NFPA 54 / ANSI Z223.1, 7.6, fig. 13: Gas Vent Termination

locations for listed Caps, 12 inches or less in size, at least 8 feet

from a vertical wall.

Termination Heights For Vents

Above Flat or Sloped Roofs

Roof Pitch

Feet

Meters

Flat to 6/12

1

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4

1.22

12/12 to 14/12

5

1.52

14/12 to 16/12

6

1.83

16/12 to 18/12

7

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8

2.44

Horizontal Overhang

2 Ft. Min.

2 Ft. Min.

Lowest

Discharge

Opening

Vent

Termination

* H

Storm

Collar

Flashing

1 inch (25.4 mm) Minimum

Clearance to Combustibles

Concentric

Vent Pipe

X

12

Roof Pitch is X/12

* H = Minimum height from roof to

lowest discharge opening of vent.