Site Preparation and Installation

24

Figure 15 Electrical field connections - outdoor condensing unit

Field supplied unit
disconnect switch.

Single or three phase
electric service not provided
by Liebert.

Field supplied 24V NEC class 2
wiring to evaporator module.

Factory wired

to components on

electric panel.

Electric service

connection

to contactor
or terminal block.

Single or three phase

electric service not

provided by Liebert.

High voltage

electric power

supply entrance.

Low voltage

electric power supply

entrance.

Earth ground connection

terminal for field wiring.

NOTE:

Refer to specification sheet
for full load amp and wire size
amp ratings.

Heat rejection connection.

Field

supplied 24V NEC class 2 wiring.
Wire connections from evaporator module:
1 24V GND System 1
2 24V Supply System 1
3 High Pressure Alarm System 1
4 Hot Gas Bypass Connection System 1
(only on units with hot gas bypass.
If no hot gas bypass, connection is
provided in the evaporator module.
Connect wire 4 and wire 2 to the
24V supply).
5 24V GND System 2
6 24V Supply System 2
7 High Pressure Alarm System 2
8 Hot Gas Bypass Connection System 2
(only on units with hot gas bypass.
If no hot gas bypass, connection is
provided in the evaporator module.
Connect wire 8 and wire 6 to the
24V supply).
9 24V GND Condenser Fan
10 24V SUPPLY Condenser Fan

DPN000135_Rev0