3.18 Run Diagnostics

By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and conduct

a test of the microcontroller circuit board from the wall box control. A review of the system inputs and

the microcontroller test can be done without interrupting normal operation.

Test Outputs

• When this feature is selected, the controller is effectively turned off. When stepping from one load

to the next, the previous load is automatically turned off. The loads can also be toggled on/off by

selecting “ENTER”. Once turned on, the output will remain on for five minutes unless toggled off

or the test outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 sec-

onds on to prevent damage.

The outputs are:

• Main Fan
• Compr1 (3-ton)
• Compr1 & HGBP1
• Compr2
• Compr2 & HGBP2
• Compr1 & Compr2
• Chill Water/Gly (if present)
• Reheat 1
• Reheat 2
• SCR Reheats (if present)
• Humidifier
• Common Alarm

Test Inputs

With the unit on and the fan running, the input states may be displayed for the following devices:

• Input Power
• High Water in Pan
• High Head Comp1
• High Head Comp2
• Air Sail Switch (requires additional factory-installed components)
• Filter Clog
• Humidifier Prob.
• Custom Alarm #1
• Custom Alarm #2
• Custom Alarm #3

!

CAUTION

Testing compressor output for more than a few seconds could damage the compressor. To

eliminate damaging the compressor during testing, DO NOT test compressor output for more

than a few seconds.

!

CAUTION

Extended unit operation in the test outputs mode for troubleshooting may cause damage to

unit. DO NOT operate unit in the test outputs mode any longer than is necessary for

troubleshooting.

NOTE
Fan turned on with all loads.