Liebert 50 & 60Hz User Manual

Page 67

Advertising
background image

Troubleshooting

59

Cooling cycle too

short

Sensor response delay too

short

Increase sensor response delay. See 3.12 - Calibrate Sensors.

Display freezes

and control pads

do not respond

Static discharge

During period of low humidity, static electricity can cause the control

program to freeze or display incorrect information. Although this is

unlikely, the control can be reset by cycling power from the disconnect

switch.

Condensate

pump does not

operate

Open or short circuit in

wiring

Find open or short circuit and repair power to pump.

Continuous

Cooling

Failed temperature sensor

Temperature display will indicate dashes. Check wiring from

temperature/humidity board (remote sensors) to the control board or

from control board to wallbox. Replace temperature/humidity circuit

board (remote sensors) or wallbox.

Continuous

Heating

Dehumidification

Humidification

Shorted wiring or failed

control board

Check wiring and/or replace control board.

Table 18

Troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy