2.1.2 Location Considerations

Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access for

routine maintenance or service. Do not attach additional devices to the exterior of the cabinet, as they

could interfere with maintenance or service.

!

CAUTION

Units contain water. Water leaks can cause damage to sensitive equipment below. DO NOT

MOUNT UNITS OVER SENSITIVE EQUIPMENT. A field-supplied pan with drain must be

installed beneath cooling units and water/glycol-cooled condensing unit.

NOTE
Do not mount units in areas where normal unit operating sound may disturb the working

environment.