2.4.3 Piping Connections and Coolant Requirements

Drain Line

A 3/4 in. (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate

drain. This line also drains the humidifier, if applicable. The drain line must be located so it will not

be exposed to freezing temperatures. The drain should be the full size of the drain connection.
The evaporator drain pan includes a float switch to prevent unit operation if drain becomes blocked.

Figure 6

Drain installation

!

CAUTION

The drain line must not be trapped outside the unit, or water may back-up in drain pan.

Drain is internally trapped.
This line may contain boiling water. Use copper or other suitable material for the drain line.

Sagging condensate drain lines may inadvertently create an external trap.

Incorrect

Incorrect

Correct

Unit

Unit

Unit

Continuous slope

away from unit

Do not externally

trap the unit

These are external traps also, although

unintentional. Lines must be rigid

enough to not bow between supports.

Humidifier drain water can approach

100° Celsius.