Condensate pump, Figure 7 condensate pump installation, Humidifier water supply line – Liebert 50 & 60Hz User Manual

Page 20: Figure 7, Condensate pump installation

Advertising
background image

Site Preparation and Installation

12

Condensate Pump

The optional condensate pump kit is required when the evaporator is installed below the level of the

gravity-fed drain line. Refer to the installation instructions provided with the condensate pump kit.

Figure 7

Condensate pump installation

Humidifier Water Supply Line

Units supplied with the optional humidifier package have a 1/4 in. (6.4 mm) FPT connection for water

inlet. Supply pressure range is 10 psig to 150 psig. Required flow rate is 1 gpm. A shut-off valve

should be installed in this line to isolate the humidifier for maintenance.

NOTE
DO NOT route humidifier supply line in front of filter box access panel.

Condensate Pump

Condensate
Pump
Support Bracket

3/4" (13mm) Hose Barb
Supplied on Pump Tank

Flexible Rubber Tubing

3/4" (13mm) FPT
Customer Connection

Condensate Drain

Evaporator or

Chilled Water

Unit

Power Supply from
Electric Service Power
Block in Fan/Coil Module.

Drain Line
(field supplied)

Notes:
1. 3/4" (13mm) Flexible Rubber Tubing Assembly (Supplied
with Pump Kit) must be installed on pump end.
2. The High Water Safety Float included with pump must be
interlocked with unit control. Wire to terminals 60 & 61 on
Evaporator terminal strip to shut down unit.

3/8" Compression Fitting
Drain Connection

FRONT OF UNIT

AIR INLET

21 1/2 "

6 5/8 "

10 9/16 "

(268.3mm)

(168.3mm)

(546mm)

DPN000239_Rev0