Microprocessor Control

41

3.17 Custom Text

To modify the two custom alarm messages select “CUSTOM TEXT”. Then select “Custom Text #1,”

“Custom Text #2” or “Custom Text #3.” Text can be up to 16 characters in length and can be either a

blank space or any of the following alphanumeric characters and symbols:

• A,B,C,D,E,F,G,H,I,J,K,L,M,N,O,P,Q,R,S,T,U,V,W,X,Y,Z
• #,%,*,-
• 0,1,2,3,4,5,6,7,8 or 9

Use the UP/DOWN arrows to select a character, then press ENTER. The cursor will move to the

next space where you may once use the UP/DOWN arrows to select another character, etc. The cus-

tom text alarm will be displayed only if the alarm is selected in Custom Alarms.

LCD Display Contrast

The level of contrast due to the viewing angle of the LCD display can be adjusted using a potentiome-

ter screw, inside the wall box next to the display.

Nonvolatile Memory

All critical information is stored in nonvolatile memory. Setpoints and setup parameters are kept

inside the microcontroller in EEPROM.

Equipment Options Switches

Equipment options are selected and enabled using DIP switches 1 through 7. These are located on the

control board near TB3. These switches are factory set and should not require any user changes. The

setting and function of the switches can be individually read on the LCD display.

NOTE
In order to update the DIP switch settings, power must be cycled off, then on, from the unit

disconnect switch.

Table 14

Equipment switch settings (unit control board)

Switch

OFF Position

ON Position

1

Step Cool

Ramp Cool

2

Step Heat

Ramp Heat

3

Not Used

Not Used

4

No GLYCOOL

GLYCOOL

5

Disable 1 stage CW

Enable 1 stage CW

6

Not used

Not used

7

1-stage

dehumidification

2-stage

dehumidification

8

Disable SCR Reheat

Enable SCR Reheat

Table 15

Switch settings (wallbox board)

Switch

OFF Position

ON Position

1

Beeper Disable

Beeper Enable

2

Not Used

Not Used

3

Not Used

Not Used

4

Enable Reheat

Disable Reheat

5

Enable Hum.

Disable Hum.

6

Enable Dehum.

Disable Dehum.

7

Disable Setback

Enable Setback

8

Enable Password

Disable Password