Troubleshooting

58

8.0

T

ROUBLESHOOTING

Table 18

Troubleshooting

Symptom

Possible Cause

Check or Remedy

Unit will not start

No power to unit

Check voltage at input terminal block.

Control voltage fuses (at

transformer) open

Locate and repair short. Replace fuses.

Float switch relay has closed

due to high water in the

condensate pan.

Check drain and line. Access through left panel. Power must be

cycled at the disconnect to reset. Check return air static pressure is

less than 0.3" wg.

Jumper not in place

Check terminal 37 and 38 for jumper or N/C contact. Check pins P39-

1 and P39-2 for jumper, or N/C firestat contact. Check pins P40-12

and 1HWAR-Com for jumper or N/C smoke detector contact.

No cooling

“Cooling” is not displayed at

the control panel.

Adjust TEMP control setpoint and sensitivity to require cooling.

Short cycle prevention

control.

Control software delays compressor 3 minutes cooling, from stop to

start

Compressor contactor not

pulling in.

Check for 24 VAC

± 2 VAC at terminals TB2 to TB1 for Compressor 1;

TB6 to TB5 for Compressor 2. If voltage, check contactor. If voltage,

check freeze stat (FR1 and FR2).

Compressor high head

pressure.

See below for cause.

Plugged filter/dryer.

Replace filter/dryer.

Low refrigerant charge.

Check pressure gauges. At low ambient temperatures, proper

refrigerant charge is very important on units with Lee-Temp receivers.

Compressor high

head pressure

Insufficient air flow across

condenser coil

Remove debris from coil and air inlets.

Water/Glycol-Cooled only:

No fluid flowing through

condenser.

Check fluid supply to regulating valve. Adjust valve if necessary.

Condenser fan not operating

Check fan operation.

Humidifier does

not operate

DIP switch not set to enable

humidifier option

See DIP switch settings Table 17.

“HUMIDIFY” not displayed

at control panel

Increase humidity control setpoint and sensitivity to require

humidification.

Defective board

Check voltage at 35-1 and 35-5 on interface board for 24 VAC

±2

VAC. If no voltage, check wiring and/or replace board. Check wiring

from control panel to board.

Failed humidity sensor

Humidity display will indicate dashes. Check wiring from temperature/

humidity board to the control board and from the wall box to the

control board. Replace wallbox or temperature/humidity circuit board

(if remote).

No water flow

Make sure switch is in Run position. Check humidifier water supply

(including filter screen) and check nylon overflow line if canister is full.

Canister fill rate is not

keeping up with the steam

output

Check fill valve screen opening and capillary tube for obstructions.

Check water supply pressure (minimum 10 psig).

Reheat will not

operate

DIP switch not set to enable

reheat option

See DIP switch settings Table 17.

“HEAT” not displayed at the

control panel

Increase temperature setpoint to require heating.

Reheat safety open,

defective reheat contact or

defective board

Check voltage at P34-4 or P34-6 to P34-10 on interface board for 24

VAC

± 2 VAC. If voltage, check reheat contactor and reheat safety. If

no voltage, check wiring and/or replace board.

Element is burned out

Turn off power. Check element continuity with Ohm meter.