LRA Linear Residential Actuator Installation Guide

- 13 -

228158 Revision X13 2-3-2009

Advanced Controller Programming

Entering Advanced Programming Mode

To access and program the Advanced Programming functions, for each
programming session, Advanced Programming must be enabled.
After exiting programming, the Advanced Programming functions
will be available on the programming display during the next
programming session unless the operator has run 50 or more
cycles. After that, Advanced Programming must be enabled again.

Maximum Run Time

The factory default for the Maximum Run Time is 99 seconds. When the
operator starts, a timer will begin counting. If a open or close limit is not
reached or an obstacle or reversing input is not received before the timer
expires, the operator will stop, the unit locks out and the alarm sounds.
The timer can be set for 10 to 99 seconds, but should be left at 99 in most
applications. Setting it too close to the actual run time may cause the time
to expire with changing ambient temperature, gate conditions, etc…

Single Button Input Setup

This function is used for selecting the operation for single button controls
and radio receivers.
The factory default sets the

SINGLE input terminal so successive inputs

will cycle the operator in OPEN-STOP-CLOSE-STOP order.
Alternately, the

SINGLE input can be set to cause the gate to OPEN

unless the gate is fully open. If the gate is fully open, the input will cause
the gate to CLOSE.

Stagger Mode

This function is used in dual gate installations only. The factory
default sets the Stagger Mode to OFF. In dual gate installations the
two operators communicate through the 3-wire

COMM LINK interface.

When using the Stagger Mode, set one operator for delayed opening and
the other operator for delayed closing. The Stagger Time programming
function (see below) sets the length of the delay.

NOTE: This function will only be displayed if dual gate operation is
selected.

Stagger Delay Time

This function is used in dual gate installations only. The factory
default sets the Stagger Time to 0 seconds (OFF). The Stagger Time
sets the delay for the Stagger Mode. The Stagger Delay Time can be set
from 1-99 seconds.

NOTE: This function will only be displayed if dual gate operation is
selected.

FUNCTION

ADVANCED PROGRAMMING FUNCTIONS

WILL NOT BE DISPLAYED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

ADVANCED

PROGRAMMING

"AD"

ADVANCED PROGRAMMING OPTIONS

WILL BE DISPLAYED

NOTE: ADVANCED PROGRAMMING

WILL STAY ENABLED AFTER

EXITING PROGRAMMING UNTIL

THE GATE CYCLES 50 TIMES

FUNCTION

SINGLE INPUT WILL OPEN OPERATOR,

IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR

SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

SINGLE BUTTON

INPUT SETUP

"SB"

FUNCTION

SETS THIS OPERATOR FOR

DELAYED OPEN

DISABLES STAGGER FUNCTION

SETS THIS OPERATOR FOR
DELAYED CLOSE

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

STAGGER

MODE

"SM"

DUAL GATES

ONLY

FUNCTION

SET STAGGER DELAY VALUE

1 TO 99 SECONDS

STAGGER TIMER DISABLED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

STAGGER

DELAY TIME

"ST"

DUAL GATES

ONLY

FUNCTION

PRESS ENTER FOR 1 SECOND

WHILE DISPLAY IS FLASHING, PRESS

UP OR DOWN TO CHANGE THE

MAXIMUM RUN TIME (10-99 SECONDS)

OPTIONS

MAXIMUM RUN

TIMER

DISPLAY SHOWS CURRENT

MAXIMUM RUN TIME SETTING

ENTER

ENTER

PRESS ENTER TO STORE THE VALUE

"RT"