4. Apply furnace cement to 4" diameter flue outlet collar on

combustion chamber and to 4" diameter collar on vent cap.

Attach 4" diameter flue outlet tube onto flue outlet collar on

combustion chamber. Attach vent cap into the 4" diameter flue

outlet tube. Attach vent cap to outside mounting plate with (3)

#10 x 1/2" screws provided.

5. Reassembly and resealing vent-air intake system is completed.
Installing a Vent Near a Window Ledge,

Other Type of Projection or on Siding (vinyl, aluminum, etc.)

Direct vent furnaces are designed to be installed on a uniform

outside wall. When the wind comes from any angle (up, down or

from either side), it must hit the vent cap equally over both the air

inlet and the flue outlet portions of the vent. Any wall projection,

such as a door or window casing, which disturbs the wind on one

side of the air inlet section will result in back pressure on the flue

section smothering the flame and eventual pilot outage.
When the vent cap is to be installed on siding or it appears that a

projection within 6" of any side of the air inlet section could shield

the air inlet section, the entire vent should be supported away from

the wall at least the distance of the projection. 2" x 4" framing

whose outside dimensions match the overall dimensions of the

mounting plate is recommended. The 2" x 4" framing protects sid-

ing from possible warpage or discoloration. All joints can then be

sealed and painted. The wall depth plus the additional depth of the

2" x 4" framing should not exceed a total depth of 13" for DV-55.

(See Figure 9)
Vinyl siding vent kit, DV-822, is available from Empire Comfort

Systems, Inc. The depth is 3", which enables the vent cap to be

extended away from siding or projections. The wall depth plus the

additional 3" depth of the vinyl siding vent cap extension should

not exceed a total depth of 13" for DV-55. (See Figure10)

Warning: When vinyl siding vent kit, DV-822 or 2" x 4"

framing is added to an existing installation (furnace is

installed) do not attempt to add sections of pipe to the flue

outlet tube or air inlet tube. An air tight seal is required for

both tubes. Refer to Parts List, page 16 to order tubes.