Stove installation, Mobile home requirements, For qualified installers only) – Lopi Answer Wood Stove User Manual

Page 13

Advertising
background image

Stove Installation

(for qualified installers only)

13

© Travis Industries

100-01166

4040907

Mobile Home Requirements

Outside air must be installed - see "Outside Air Requirements" on page 11

Chimney connector and chimney must be one of the following types:

AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)

Straight Installations

a

b

d

e

Corner Installations

c

f

NOTE:
Measure clearances to the stove top.

Figure 8

Minimum Clearance
(See the illustration above)

Reduced Clearance
Connector

A

Sidewall to stove

13"

B

Backwall to stove

9"

C

Cornerwall to stove

7-1/2"

D

Connector to sidewall

21-1/2"

E

Connector to backwall

11-1/2"

F

Connector to cornerwall

16-1/2"

If using offsets, use the connector clearance listed in Figure 9, not the
connector manufacturer's clearance
.

The appliance must be secured to the floor (consult your building official).
Secure the outside air boot to the floor and stove to insure the stove does
not dislocate.

Mobile home installations require a spark arrester at the chimney
termination.

The appliance must be grounded to the chassis of the mobile home
(consult your building official).

WARNING:DO NOT INSTALL IN SLEEPING ROOM.

CAUTION:THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.

12” Min.

Connector Clearance
(as outlined above)

Stove Clearance
(as outlined above)

Figure 9