Liebert iCOM Microprocessor TM-10098 User Manual

Page 94

Advertising
background image

iCOM

Control Training and Service Manual

007 LOSS OF

AIRFLOW

not enough airflow
through the unit.
this event can be set to
switch off the unit or to
disable hum and electric
heat.

Alarm

yes, if

set to

shut

down

yes

yes, only if

set to

"disable"

008 CLOGGED

FILTERS

air filters are dirty

Warning

no

no

-

018 HIGH ROOM

TEMP

actual return air
temperature (value from
std. sensor) is higher
than the threshold

Warning

no

no

-

019 LOW ROOM

TEMP

actual return air
temperature (value from
std. sensor) is lower than
the threshold

Warning

no no

-

020 HIGH ROOM

HUM

actual return air humidity
(value from std. sensor)
is higher than the
threshold

Warning

no

no

-

021 LOW ROOM

HUM

actual return air humidity
(value from std. sensor)
is lower than the
threshold

Warning

no no

-

022 HIGH TEMP

SENSOR A

actual temperature
(value from optional
sensor A) is higher than
the threshold

Warning

no

no

-

023 LOW TEMP

SENSOR A

actual temperature
(value from optional
sensor A) is lower than
the threshold

Warning

no no

-

024 HIGH HUM

SENSOR A

actual humidity (value
from optional sensor A)
is higher than the
threshold

Warning

no

no

-

025 LOW HUM

SENSOR A

actual humidity (value
from optional sensor A)
is lower than the
threshold

Warning

no no

-

026 UNIT HRS

EXCEEDED

actual working hours of
the fan are higher than
the threshold set.

Warning

no

no

-

027 COMP 1 HRS

EXCEEDED

actual working hours of
compressor 1 are higher
than the threshold set.

Warning

no no

-

93