Liebert iCOM Microprocessor TM-10098 User Manual

Page 98

Advertising
background image

iCOM

Control Training and Service Manual

098 DIG SCROLL2

HIGH TEMP

Digital Scroll compressor
#1 shut off because of
high temperature (sensor
is inside the
compressor).

Alarm

no

yes

yes

(broken co
will remain

off)

103 SHORT CYCLE compressors are

requested from control to
start too often - control is
unstable.

Message

- no

-

104 SMOKE

DETECTED

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

105 WATER

UNDER
FLOOR

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

106 COND PUMP-

HIGH WATER

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

107 LOSS OF

FLOW

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

108 STBY GLYCOL

PUMP ON

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

109 STANDBY

UNIT ON

customer input is active.

Alarm

no

yes

yes (if not

disabled

externally)

110 HW/HG HRS

EXCEEDED

actual working hours of
hot water heat / hot gas
reheat are higher than
the threshold set.

Warning

no

no

-

111 EL HEAT1 HRS

EXCEEDED

actual working hours of
electrical heater stage 1
are higher than the
threshold set.

Warning

no no

-

112 EL HEAT2 HRS

EXCEEDED

actual working hours of
electrical heater stage 2
are higher than the
threshold set.

Warning

no

no

-

113 EL HEAT3 HRS

EXCEEDED

actual working hours of
electrical heater stage 3
are higher than the
threshold set.

Warning

no no

-

97