For left rear piping – LG A2UH243FA0(LMU240HE) User Manual

Page 24

Advertising
background image

24 Multi type Air Conditioner

Flaring Work and Connection of Piping

1. Route the indoor tubing and the drain hose to the required

piping hole position.

2. Insert the piping, drain hose, and the connecting cable into

the piping hole.

3. Insert the connecting cable into the indoor unit.

• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection

later.

4. Tape the drain hose and the connecting cables.

5. Indoor unit installation

• Hang the indoor unit from the hooks at the top of the

installation plate.

• Insert the spacer etc. between the indoor unit and the

installation plate and separate the bottom of the indoor
unit from the wall.

Connecting the piping to the indoor unit and the drain
hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the

flare nut by hand.

2. Tighten the flare nut with a wrench.

3. When extending the drain hose at the indoor unit, install

the drain pipe.

For left rear piping

Drain pipe

Connecting

cable

1

2

Installation plate

Spacer

Indoor unit

8cm

Indoor unit tubing

Flare nut

Pipes

Wrench

Indoor unit tubing

Connection pipe

Flare nut

Open-end wrench (fixed)

Vinyl tape

Adhesive

Drain hose

Indoor unit drain hose

(narrow)

mm

inch

kg.m

Ш6.35

1/4

1.8

Ш9.52

3/8

4.2

Outside diameter

Torque