Charging – LG A2UH243FA0(LMU240HE) User Manual

Page 38

Advertising
background image

38 Multi type Air Conditioner

Charging

■ Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor

line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant
charge has to be adjusted.

■ Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added

or removed based on 20g(0.22oz) of R-410A per meter(foot).

Example:

A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge
adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.

24k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

Capacity (Btu/h)

Max total length

of all pipes

(A+B)

Max length of

each pipe (A/B)

Min length of

each pipe (A/B)

Max Elevation

between each indoor

unit and outdoor unit

(h1)

Max elevation

between indoor

units (h2)

Additional

Refrigerant

Charging

Advertising