74 Multi type Air Conditioner

Troubleshooting Guide

Error

Title

Cause of error

Check point & Normal condition

code

33

D-Pipe Temp. High

• Discharge sensor

temp. high

• Check the discharge pipe sensor.
• Check the install condition for over load.
• Check the leakage of refrigerent.
• Check the SVC V/V open.

Error

Title

Cause of error

Check point & Normal condition

code

51

Capacitor error

• Over Capacitor com-

bination

• Check the indoor unit capacity.
• Check the combination table

Check Point

1. Check the indoor unit capacity.

2. Check the combination table.

★ In the tropical model case
➔ single cycle has no error for over capacity.

Check Point

1. Check the install condition for over load.

2. Check the SVC V/V open.

3. Check the leakage of refrigerent.

4. Check the constant compressor.

COMP OFF

LEV OPEN(16PULSE/MIN)

LEV OPEN(10PULSE/MIN)

NORMAL

A2UH243FA0/A2UC243FA0

115

°C(239°F)

100

°C(212°F)

95

°C(203°F)