ESAB 453cc User Manual

Page 11

Advertising
background image

11

Input &

GND

Fuse Size

Conductor*

Am ps

CU/AWG

208

64

No. 6

90

220

61

No. 6

80

230

58

No. 6

80

482cc

400

33

No. 10

40

460

29

No. 10

40

575

23

No. 12

30

208

82

No. 4

120

220

77

No. 4

120

230

74

No. 4

120

582cc

400

43

No. 8

70

460

37

No. 8

60

575

30

No. 10

50

* Sized per National Code for 75

o

C rated copper conductors @ 40

o

C

Not more than three conductors in a raceway or cable. Local codes
should be followed if they specify sizes other than those listed above.

Rated Input

100% Duty Cycle Rating

Volts

Am ps

Figure 2.1 Connecting Primary Power Leads

Table 2.1 Recommended Input Conductor Size and

Line Fuses

Figure 2.2 Input Terminal Board

*

Double Link Provided

( ) Connections for 50 Hz

230/460 (220/400)V illustrated with voltage links in
the factory supplied 460 volt configuration.

SECTION 2

INSTALLATION

453CC

553CC

Strain Relief

Rear Panel (Inside View)

TB3 Located on
Fan Bracket

Recommended Cable Strip Lengths

Ground Fault
Switch*

SWITCH

GROUND LUG

NUT

HORSESHOE

5"

10"

Advertising