Pump packages & expansion tank - options, Figure 8 pump package, Figure 9 pump mounting – Liebert EMERSON 60 HZ User Manual

Page 17: Notes, Figure 10 expansion tank, Expansion tank- (p/n 1c16717p1), Table 8 pump data, Figure 11 pump curve, 60 hz, Ackages, Xpansion

Advertising
background image

13

P

UMP

P

ACKAGES

& E

XPANSION

T

ANK

- O

PTIONS

Figure 8

Pump package

Figure 9

Pump mounting

Notes

1. Single pump packages are

17-1/4" (438.2mm) wide. Dual

pump packages are 32-1/4"

(819.2mm) wide.

2. Mounting holes are 15-11/32"

(389.7mm) apart on single

pump packages and

30-11/32" (770.7mm) apart on

dual pump packages.

3. 7-1/2hp dimensions not

shown—consult factory.

Provided on dual

pump package only

Pump suction

connections

Pump

discharge

connections

30-1/4"

(768.4mm)

See

Note 1

19"

(483mm)

See

Note

2

Pump Package

Mounting

1/2" (12.7mm)

diameter holes

23"

(584.2mm)

3/4"

(19.1mm)

3-1/2"

(88.9mm)

Figure 10 Expansion tank

Expansion Tank- (P/N 1C16717P1)

This tank, included in a standard pump package, has an internal volume of 8.8 gal. (33 l)

and a maximum pressure of 100 psi (690 kPa).
This tank is sized for a typical “open” system with a fluid volume of less than 75 gal.

(280l). When used in a “closed” system, volumes of up to 140 gal. (910l) can be accommo-

dated. The use of a safety relief valve, field supplied, is recommended for systems

“closed” to atmospheric venting. Other piping accessories for filling, venting, or adjusting

the fluid in the system, are recommended, but not included.

Figure 11 Pump curve, 60 Hz

Table 8

Pump data

Pump

Model

Connections

HP

Electric @ 60Hz

NPT

Suction

Female

Discharge

PH

208

FLA

230

FLA

460

FLA

575

FLA

3/4

1-1/4"

3/4"

3/4

1

7.6

6.9

N/A

N/A

3/4

1-1/4"

3/4"

3/4

3

3.5

3.2

1.6

1.3

1-1/2

1-1/4"

3/4"

1-1/2

3

6.6

6.0

3.0

2.4

2

1-1/4"

3/4"

2

3

7.5

6.8

3.4

2.7

3

1-1/2"

1"

3

3

10.6

9.6

4.8

3.9

5

1-1/2"

1-1/4"

5

3

16.7

15.2

7.6

6.1

7-1/2

3"

3"

7-1/2

3

24.2

22.0

11.0

9.0

To Calculate Total Pump and Drycooler Full Load Amps (FLA):

Total FLA = Pump FLA + Drycooler FLA

To Calculate Total Pump and Drycooler Wire Size Amps (WSA)

Total WSA = Largest Motor FLA x 1.25 + Sum of other Motor FLA values

To Calculate Total Pump and Drycooler Maximum Overcurrent Protective Device (OPD)

Total OPD = Largest Motor FLA x 4.0 + Sum of other Motor FLA values
Select standard fuse size (15A, 20A, 25A, 30A, etc.)

0

10 20 30 40 50 60 70 80 120 160 200 250 300 400

20

100

40

60

80

120

160

140

180

Flow Rate - GPM

To

ta

l Hea

d

-

ft

. w

ater