Supplementary application data, Table 9 room dew point temperatures, Table 10 glycol concentration at various ambients – Liebert EMERSON 60 HZ User Manual

Page 18: Table 11 volume in standard tube, Maintenance guidelines, Important, Upplementary, Pplication, Aintenance, Uidelines

Advertising
background image

14

S

UPPLEMENTARY

A

PPLICATION

D

ATA

Table 9

Room dew point temperatures

Dry bulb

°F (°C)

Wet bulb

°F (°C)

Rel. hum.

%

Dew point*

°F (°C)

70

57.2

45

41.1

70

58.5

50

50.5

72

58.9

45

50.0

72

60.0

50

52.4

75

61.2

45

52.4

75

62.5

50

55.0

* Minimum glycol temperature before condensation will occur

Table 10

Glycol concentration at various
ambients

% Glycol

by volume

0

10

20

30

40

50

Freezing

point °F

32

25

16

5

-10

-32

Apparent

specific

gravity

@50°F

1.000 1.014 1.028 1.042 1.057 1.071

Table 11

Volume in standard tube

Type “L” copper tube

Diameter (in.)

Volume

Outside

Inside Gal/ft

(L/m)

.50

0.430

0.0075

(0.09)

.625

0.545

0.0121

(0.15)

.75

0.666

0.0181

(0.22)

.875

0.785

0.0251

(0.31)

1.125

1.025

0.0429

(0.53)

1.375

1.265

0.0653

(0.81)

1.625

1.505

0.0924

(1.15)

2.125

1.985

0.161

(2.00)

2.625

2.465

0.248

(3.08)

3.125

2.945

0.354

(4.40)

3.625

3.425

0.479

(5.95)

4.125

3.905

0.622

(7.73)

M

AINTENANCE

G

UIDELINES

Restricted airflow through the

drycooler coil will reduce the oper-

ating efficiency of the unit and

can result in high fluid tempera-

tures and loss of cooling.
Clean the drycooler coil of all

debris that will inhibit air flow.

This can be done with compressed

air or commercial coil cleaner.
Check for bent or damaged coil

fins and repair as necessary. In

winter, do not permit snow to

accumulate around the sides or

underneath the drycooler.
Check all fluid lines and capillar-

ies for vibration isolation. Support

as necessary.

Visually inspect all fluid lines for

signs of fluid leaks.
Inspect the motor/fan assembly to

insure bearings are (free) and

motor is secure within the mount.
The glycol in drycooler systems

level must be periodically

checked. At the high point of the

system check:

For positive pressure.

For air to be vented.

For an unlogged expansion

tank. A fluid sample for

proper concentrations of anti-

freeze and inhibitors.

The first three checks may give

indication of leaks in the system.

Important

When ordering replacement parts

for heat rejection equipment, it is

necessary to specify unit model

number - serial number - voltage.
Enter this information below for

future use.

Model No.

Serial No.

Voltage