Selection procedure, Example, Table 2 determining actual btuh and mbh – Liebert EMERSON 60 HZ User Manual

Page 7: Table 3 altitude correction, Election, Rocedure, Table 2, Determining actual btuh and mbh, Table 3, Altitude correction

Advertising
background image

3

S

ELECTION

P

ROCEDURE

Table 4 shows the performance specifications for

Liebert drycoolers using a 40% by volume ethylene

glycol solution at an average fluid temperature of

115°F with flow rates from 1.5 to 3 GPM/circuit and

at standard air (.075 lbs/ft

3

). Figure 2 and Figure 3

offer correction factors to Table 4 for average fluid

temperatures and glycol percentages other than

115°F and 40%. Table 3 correction factors may be

used for performance at altitudes above sea level.

For cooling applications other than shown, contact

the Liebert Heat Transfer Division.
To select a drycooler from the tables in this

bulletin, the following information must be known:
1. Fluid Flow Rate (GPM).
2. % Ethylene Glycol (% EG).
3. Design Air Temperature at the Drycooler (EAT).
4. Entering and Leaving Fluid Temperatures (EFT,

LFT) or Total Heat Rejection (BTU/HR) and one

of the Fluid Temperatures.

5. ITD (Initial Temperature Difference) = EFT -

EAT

From the known data, calculate the following:

Average Fluid Temperature (AFT) = (EFT +

LFT)/2.

Heat Rejection (BTUH) = Fluid Temp. Diff. x

GPM x BTU/GPM Factor (Table 2).

(Leaving Air Temperature should be lower than

145°F for proper motor operation.)
Using Table 4 to select a drycooler
Calculate required MBH/ITD with corrections for

glycol % and average fluid temperature.

2. Locate Model No. in Table 4 having a GPM

range within the required flow rate and an MBH

equal to or greater than required. This gives an

approximate size.

3. Divide the given GPM by the “No. of circuits” of

the drycooler selected. The result is “GPM/CIR”

and should be in the range of 1-1/2 to 3.

4. In Table 4, look up the model selected above and

under “GPM/CIR” find the actual MBH. You may

interpolate between columns.

The MBH found should be equal to or greater than

the “required MBH /ITD.”
If the MBH is less than required, repeat from Step 2

with a larger model. You may wish to repeat from

Step 2 with a smaller model for the most economical

selection meeting the required MBH/ITD.
Pressure Drop - After selecting a model, look up

the unit pressure drop following Step 3 and 4 above.

Multiply the pressure drop found by the Figure 3

correction factor. If the product is higher than your

system design, go back to Step 2 and select a model

with more circuits. This may be the same, or larger,

unit.

Example

Cool 40 GPM 20% ethylene glycol and water solution

from 125(F) to 115(F). Design EAT = 95(F).
Calculate:

BTUH = (125 - 115) x (40 GPM) x (480 BTU/

GPM)

BTUH = 192,000
AFT = (125 + 115)/2 = 120(F)
From Figure 2, corr. factor for 120 AFT and

20% EG = 1.04

2. Locate model in Table 4. Models 092 through

139 fall into the GPM range but do not have the

MBH capacity. Model 174 with 16 circuits is the

smallest model meeting both the GPM range and

MBH requirements.

3. GPM/CIR = 40 GPM/16 CIR = 2.5 GPM/CIR.
4. In Table 4, Model 174 with 16 circuits at the 2.5

GPM/CIR column provides 6.9 MBH/ITD, which

exceeds the required MBH/ ITD of 6.15.

Pressure Drop = 10.5 ft. (from Table 4) x 0.93 (from

Figure 3) = 9.8 ft. H

2

O.

Leaving Fluid Temperature =
EFT - BTUH

(GPM) (BTU/GPM)

Other useful information:

Leaving Air Temp. = EAT +

Drycooler BTUH

(1.08) (Drycooler CFM)

1. Required MBH/ITD =

BTUH

(EFT - EAT) (1000) (Fig. 1 Factor)

Table 2

Determining actual BTUH and MBH

% Glycol

Solution

0%

10%

20%

30%

40%

50%

BTUH/GPM

500

490

480

470

450 433

Table 3

Altitude correction

Alt. (Ft.)

0 1000 2000 5000 8000 12000 15000

Corr. Fact.

1

.979

.96

.9

.841

.762

.703

1. Required MBH/ITD =

192,000 BTUH

(125-95) (1000) (1.04)

Advertising