5.5.10 Edit the Breaker Properties

The Breaker Properties box displays the breaker name, rating, other parameters and alarm setpoints.

To view or change parameters and alarm setpoints of a breaker:

• Click on the breaker in the left pane. When selected, the breaker has a yellow outline.
• Refer to the following table to make changes.

• When finished, click Install to Unit to upload the changes to the Liebert LDM.

Parameter

Description

To make a change:

Breaker

Name

The name of the selected breaker. The default

names are BREAKER #01, BREAKER #02, etc.

• Click in the Breaker Name box, click Edit and

enter a name, then click Apply.

Position

The location of the selected breaker on the

panelboard.

(Cannot be edited)

Number

of Poles

The number of poles selected when the breaker was

added to the panelboard.

(Cannot be edited)

Breaker

Rating

The amperage for which the circuit breaker is rated.

The default is 20A.

• Click in the Breaker Rating box, click Edit and

enter a value, then click Apply.

Phase

Overcurrent

Alarm

Percentage of the breaker rating that triggers an

overcurrent alarm. This value must be higher than

the Phase Overcurrent Warning.

• Click in the Phase Overcurrent Alarm box,

click Edit and enter a value, then click Apply.

Phase

Overcurrent

Warning

Percentage of the breaker rating that triggers an

overcurrent warning. This value must be lower than

the Phase Overcurrent Warning.

• Click in the Phase Overcurrent Warning box,

click Edit and enter a value, then click Apply.

Phase

Undercurrent

Alarm

Percentage of the breaker rating that triggers an

undercurrent alarm. The default is 0 (zero). Indicates

no current is flowing through the breaker—either the

breaker has tripped or the equipment has shut down.

• Click in the Phase Undercurrent box, click Edit

and enter a value, then click Apply.

Neutral Current

Alarm

Percentage of the breaker that triggers a neutral

current alarm.

• Click in the Neutral Current Alarm box, click

Edit and enter a value, then click Apply.

Ground Current

Alarm

Amperage that triggers a ground current alarm.

• Click in the Ground Current Alarm box, click

Edit and enter a value, then click Apply.

NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit

button is clicked.