2 panel board voltage-current board (pbvi), Table 1 ct matrix for the liebert ldm, Panel board voltage-current board (pbvi) – Liebert Distribution Monitoring LDM User Manual

Page 9: Ct matrix for the liebert ldm, Warning

Advertising
background image

Major Components

5

3.2

Panel Board Voltage-Current Board (PBVI)

The PBVI board monitors two panelboards and provides the voltage attenuators for the two panel-

board voltages. The two sets of panelboard main breaker CTs are connected to the PBVI board.

Connections for the 18 large branch CTs are located on the PBVI board. The nine CTs on the A side of

the board are normally associated with the A-side voltages for power calculations. The B-side CTs are

normally associated with the B-side voltages. A cross-configuration tool allows changing that associa-

tion for subfeeds.
The 18 large branch CT inputs can also be used to monitor up to three subfeed circuit breakers. This

is configured using the Configuration tool (see 5.5 - Using the Configuration Tool). The CTs from

the B side of the PBVI are cross-configured to the A side so that the three sub-feeds appear within the

A-side panelboard register space. The 18 large branch breakers require CTs with 1A secondary.

!

WARNING

Before connecting a large CT to the PBVI board, note the CT MUST have 1A secondary.

Connecting a 5A secondary type CT will damage the board and the CT.
To ensure the proper current ratio and accuracy, the CTs should be purchased through

Emerson Network Power. See Table 1 for details. Contact your local Emerson Network

Power representative or call Liebert Services at 1-800-LIEBERT (1-800-543-2378).

Table 1

CT matrix for the Liebert LDM

Part Number

Description

Phase CT

Ground CT

Neutral CT

528415G1-L

3 pole 100A Subfeed Breaker 5W CT Kit 23" Frame

100:1

100:1

200:1

528415G2-L

3 pole 125-225A Subfeed Breaker 5W CT Kit 23" Frame

200:1

100:1

500:1

528415G3-L

3 pole 250-400A Subfeed Breaker 5W CT Kit 23" Frame

500:1

100:1

500:1

531461G6-L

3 pole 0-100A I-Line & Subfeed Breaker 5W CT Kit 47" Frame

200:1

100:1

200:1

531461G9-L

3 pole 125-225A I-Line & Subfeed Breaker 5W CT Kit 47" Frame

200:1

100:1

500:1

531461G12-L

3 pole 250-400A I-Line & Subfeed Breaker 5W CT Kit 47" Frame

500:1

100:1

500:1

531461G18-L

3 pole 0-225A I-Line Breaker 3W CT Kit 47" Frame

200:1

531461G19-L

3 pole 250-400A I-Line Breaker 3W CT Kit 47" Frame

200:1

528461G13-L

1 pole 0-100A Branch Breaker CT Kit

100:1

528415G14-L

2 pole 0-100A Branch Breaker CT Kit

100:1

528415G15-L

3 pole 0-100A Branch Breaker CT Kit

100:1

Advertising