2 special procedures, 1 condenser cleaning, When to clean – Liebert Air Cooled User Manual

Page 38: What to use, How to clean, Special procedures, Condenser cleaning

Advertising
background image

System Maintenance

34

6.2

Special Procedures

6.2.1 Condenser Cleaning

Keeping the outdoor condenser coils clean is an important factor in maintaining peak efficiency, reli-

ability and long life of the equipment. It is much easier to keep up on frequent cleanings rather than

wait until heavy build up has occurred which may create head pressure problems with the evaporator

units.

When to Clean

Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions

such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard

monthly preventive maintenance schedule, a visual inspection of the coil is recommended to monitor

conditions.

What to Use

The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and

cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy build

up on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and

sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower

pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins

could result. If a cleaner is required, we recommend a non-acidic type cleaner be used. Acid-type

cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow the

use of acidic cleaners for environmental reasons.

How to Clean

The absolute best way to clean coils is from the inside out. This requires disconnecting the power sup-

ply from the condenser before working on the unit. The fan guards and fan blades must be removed to

gain access to the coil surface. The sprayer can then be worked across the coil using the water/clean-

ing solution, pushing the dirt and debris out the bottom of the coil. Although this does extend the time

involved, the results are well worth it. This method should be used at least once a year. Spraying the

coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins and con-

tinue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for

an extended time. A pre-scheduled shutdown with the operator may be in order. If you are using a

cleaner along with the spraying process, follow recommended manufacturer instructions and be sure

to rinse the coil thoroughly. Any residue left on the coil can act as a magnet to dirt.
Reinstall and secure the fan blades and fan guards after the cleaning is finished. Last, reconnect the

power supply to the condenser.