Site Preparation

8

Figure 6

Typical condenser footprint—dimensions

Figure 7

Piping connection locations for 1-, 2-, 3- and 4-fan VFD Control and Fan Speed Condensers

2”

(50.8mm)

9/16" (14mm)

Typical Diameter

1-3/4”

(44.5mm)

4-1/4”

(108mm)

1-3/4”

(44.5mm)

4-1/4”

(108mm)

1”

(25.4mm)

2”

(50.8mm)

Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
Support field piping separately
to avoid coil damage and loss
of charge.

Leaving
Liquid Line

Entering
Hot Gas Line

Traps to extend above
coil base by a minimum
of 7-1/2" (190mm)

Inverted Traps
(field-supplied)

See
Detail
A-A

DPN000665
Rev. 02

Detail A-A

Metal
clamp

Isolator