Inspection and Installation

20

3.6.2 Low Voltage Control Wiring

NOTICE

Risk of control malfunction. Can cause improper unit operation. Make sure that all low

voltage electrical wiring has been performed per the schematic diagram provided and that all

low voltage wiring connections are tight.

A control interlock between the condenser and the indoor cooling units is required. Field-supplied cop-

per wire (Class 1 for TCDV models and Class 2 for all other condenser models) is required for connec-

tion between like-numbered terminals 70 & 71 on both units. Wiring must be sized so that the voltage

drop in the circuit does not exceed 1 volt. See Figures 19, 20 and 21 and indoor unit manual for loca-

tion of terminals on condensers and indoor units.

3.6.3 Low Voltage Monitoring Wiring—TCDV Only

Condensers with monitoring terminals may be wired with Class 1 copper wire to the indoor cooling

unit or other monitoring panel. Wiring must be sized so that the voltage drop in the circuit does not

exceed 1 volt. Dry contacts close when a monitored event occurs. Consult condenser electrical sche-

matic, supplied with the unit, for details.
Contact closure on VFD Drive monitoring terminals indicates a permanent VFD fault. A factory-pro-

grammed VFD must be used as the replacement.
Contact closure on TVSS monitoring terminals may indicate unit trouble ranging from electrical sup-

ply issues to TVSS replacement required. A properly trained and qualified electrician is required.

3.7

Electrical Connections

Electrical service is required for all models. Electrical service shall conform to national and local elec-

trical codes. Refer to equipment nameplate regarding wire size and circuit protection requirements.

Refer to electrical schematic when making connections. Refer to Figures 19, 20 and 21 for electrical

service entrances into unit.
A manual electrical disconnect switch should be installed in accordance with local codes. Consult local

codes for external disconnect requirements.

NOTICE

Installation and service of this equipment should be done only by properly trained and

qualified personnel who have been specially trained in the installation of air conditioning

equipment.

NOTICE

Use copper wiring only. Make sure that all conections are tight.

Table 8

Lee-Temp receiver electrical data, 50Hz and 60Hz

Rated Voltage - Single Phase

120

200/208/230

Watts/Receiver

150

300

450

150

300

450

Full Load Amps

1.4

2.8

4.2

0.7

1.4

2.1

Wire Size Amps

1.8

3.5

5.3

0.9

1.8

2.7

Maximum Overcurrent

Protection Device, Amps

15

15

15

15

15

15

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit. Unit

contains lethal voltage in some circuits. Use voltmeter to make sure power is turned Off

before making any electrical connections.