System Maintenance

35

6.2.2 Maintenance Inspection Checklist

Signature: _________________________________________________________________________________________

Make photocopies of this form for your records

Date:____________________________________

Prepared By:____________________________________

Model #:_________________________________

Serial Number:__________________________________

NOTE
Regular inspections are necessary to ensure that the cooling fins are clean. Should inspection

reveal dirt or corrosion, appropriate cleaning should be performed.

Monthly

Semiannually

Condenser

___ 1. Coil surfaces free of debris
___ 2. Fans free of debris
___ 3. Fan motors securely mounted
___ 4. Motor bearings in good

condition

___ 5. Check all refrigerant lines and

capillaries for vibration

isolation. Support as

necessary.

___ 6. No refrigerant leaks.

Condenser Electrical Panel

___ 1. On TCDV models, check TVSS

protection status indicator

light.

Condenser

___ 1. Complete all monthly items
___ 2. Piping in good condition
___ 3. Inspect refrigerant lines for signs of oil

leaks. Repair leaks as found.

___ 4. Check refrigerant charge level in each

receiver tank (if equipped), based on

procedures in the indoor unit’s manual.

Continuous system operation required.

___ 5. Wash coil as needed
___ 6. Repair bent or damaged fins.

Condenser Electric Panel

___ 1. Check all electrical connections
___ 2. Check contactors for pitting
___ 3. Operational sequence/setpoints

Fan Motors

___ 1. Motor #1 amp draw __________ amps
___ 2. Motor #2 amp draw __________ amps
___ 3. Motor #3 amp draw __________ amps
___ 4. Motor #4 amp draw __________ amps
___ 5. Motor #5 amp draw __________ amps
___ 6. Motor #6 amp draw __________ amps
___ 7. Motor #7 amp draw __________ amps
___ 8. Motor #8 amp draw __________ amps

Notes