Table 9 troubleshooting, Table 9, Troubleshooting – Liebert Air Cooled User Manual

Page 40

Advertising
background image

System Maintenance

36

Table 9

Troubleshooting

Symptom

Possible Cause

Check or Remedy

Condenser will not start

No power to condenser

Check voltage at input terminal block

Circuit breaker for low voltage

transformer in condenser is tripped

Locate problem in condenser electrical

panel and repair

No low voltage signal to/from indoor unit Locate open circuit and repair

Low indoor unit

suction pressure

Insufficient refrigerant in system

Check for leaks, repair, and add refrigerant

Fan-cycling ambient thermostats

setpoints too low

Check schematic for recommended

setpoints and adjust.

Low discharge pressure

Faulty head pressure control valve

or condenser FSC/VFD control

Replace if defective

High discharge pressure

Dirty condenser fins

Clean coil

Condenser fans not operating

Check for low voltage signal from indoor unit
Check fan motors and fuses
Check for correct ambient thermostat

setpoints, as applicable.

High refrigerant charge

Check refrigerant charge

VFD Condenser trips out

on overvoltage

(OU displayed on VFD

controller)

Supply voltage is Delta configuration

or is ungrounded/high impedance

Shut off AC voltage, locate the VFD, pull out

the EMC tab and reconnect power

TVSS indicator lights are

extinguished or red LED is

illuminated and monitoring

terminals 11/12 are closed

No voltage or improper phasing exists

at condenser

Check voltage at input terminal block

Electrical connections to TVSS are

faulty

Locate connection problem and repair

A surge exceeding the rating

of the TVSS has occurred

Replace TVSS and inspect other

components for damage and replace them if

necessary