Figure 2 – Liebert Air Cooled User Manual

Page 7

Advertising
background image

Introduction

3

Figure 2

Typical system configuration—indoor unit and outdoor condenser and field piping

Lee-Temp Receiver

Fan Speed and VFD

Lee-Temp

Service
Valve

External
Equalizer

Liquid

Sensing
Bulb

Inverted trap on discharge & liquid
lines to extend above base of coil
by a minimum of 7-1/2” (190mm).

Field-installed relief valve (s) required
for 50 Hz EU CE units rated maximum
480 PSIG (33 Bar).

* Isolation
valve

* Traps every
25ft (7.6m)
of rise

Fusible
Plug

Suction

Hot Gas Discharge

Liquid Return

Filter Dryer

Sight Glass

Solenoid
Valve

Expansion
Valve

DPN000798
Rev. 2

Condenser Coil

(Fan Speed

and VFD)

Condenser Coil

(Lee-Temp)

Evaporator Coil

Compressor

Service
Valve

Check
Valve

* Isolation
valve

28-42kW Digital Solenoid Valve

53-70kW Digital

Solenoid Valve

Factory Refrigerant Piping
Field Refrigerant Piping

Service/Schrader (Access) Connection No Valve Core

Note: Schematic representation shown . Do not use for specific connection locations .

Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .

Service/Schrader (Access) Connection With Valve Core

Liquid Return

Hot Gas

Discharge

Head Pressure

Control Valve

Check
Valve

Relief
Valve

Service
Valve

Components are not supplied by
Liebert, but are recommended
for proper circuit operation and
maintenance.

*

Pitch horizontal hot gas piping
1/2" per 10 ft. (42mm per 10m)
in direction of refrigerant/oil flow.