PB Heat MI/MIH series User Manual

Page 14

Advertising
background image

12

Figure 4.2: Venting with Vent Damper in Vertical Position

Figure 4.3: Venting with Vent Damper in Horizontal Position

C. VENT PIPING AND CHIMNEY

1. Install vent piping in accordance with Venting of

Equipment part of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, sections 7.2, 7.3 or 7.4 of
CAN/CSA B149.1, Natural Gas and Propane
Installation Code
, or applicable provisions of the
local building codes.

2. Inspect the existing chimney and lining for structural

soundness, corrosion and perforations. Repair as
necessary.

3. Install vent pipe to slope upward at least 1/4” per

lineal foot (21 mm per meter) between the draft
hood outlet and the chimney.

4. Before connection of joints, inspect the vent pipe

interior for foreign objects such as tools, equipment,
rags, etc. and remove if present.

5. Insert vent pipe into but not beyond the inside wall

of the chimney flue.

6. Do not connect vent connectors serving appliances

vented by natural draft into any portion of
mechanical draft systems operating under positive
pressure.

7. Support horizontal portions of the venting system to

prevent sagging by use of metal strapping or
equivalent means. Locate supports at no more than
4 foot (1.2 meter) intervals.

VENTING

Advertising