A. BOILER SUPPLY AND RETURN

1. Size the supply and return to suit the system. A

typical piping arrangement is shown in Figure 3.1.
Refer also to the I=B=R Guide - Residential
Hydronic Heating Installation/Design and the PB
Heat Water Survey for additional guidance during
water piping installation.

2. Return Piping:

Pipe the drain valve to a tee, provided, and the
1-1/4 NPT return tapping near the bottom of the left
section. Pipe the return to the tee. Pipe the drain
valve nipples and tee to the 1-1/4 NPT return
tapping as shown in Figure 3.1.

3. Supply Piping:

Pipe the supply to the 1-1/2 NPT supply tapping at
the top and rear of the boiler.

4. When system return water temperature will be below

130°F (54°C), pipe the boiler with a bypass
arrangement to blend the system return and hot
supply to obtain at least 130°F (54°C) entering the
boiler. For more information on bypass piping,
consult the PB Heat Water Survey.