Patterson-Kelley TBIG-03 User Manual

Page 7

Advertising
background image

Installation

*

*

*

*

*

*

propane
connection
manual
shutoff

natural gas
connection
manual
shutoff

regulator

low gas
pressure switch

motorized gas valve
(propane)

low gas
pressure switch

motorized gas valve

motorized gas valve
(natural gas)

high gas pressure
switch

pressure tap

burner

secondary
shutoff, manual

pilot
shutoff

regulator

pilot regulator and
solenoid valve

mechanical link
to control air
(Lo-Hi-Lo only)

Items with symbol must be
vented to outside. Refer to the
drawings packed with your
boiler for additional information.

leak test
valves

n.o. vent valve
(I.R.I. only)

Figure 4-1 Piping Schematic for the Twin-Fuel Gas Train

4.0 I

NSTALLATION


Gas Train Connection Sizes

Natural Gas

Propane

700/1000/1200

Series

1 1/4"

1"

1500/1700/2000

Series

2"

1 1/4"



4.1 G

ENERAL


Installation of the twin-fuel Gemini™ boiler is similar
to that of the single-fuel model. Refer to “Thermific

â

Gas-Fired Boiler - Installation and Owner’s Manual -
TBIG” pages 2 through 10.

The following procedures are different from those for
the single-fuel model, and are described in this Sec-
tion:

· Gas Piping

Gas Bleeds and Vents

· Pre-Start Check List
· Pre-Start Safety Checks and Adjustments

Test of Ignition Safety System

Test of Low Water Cutoff

Test of High Limit Control

Test of Gas Pressure Switch


- 5 -

Advertising