Specifications

Table 4. Electrical Output

Power Levels (rated at

500VA, 320W

nominal inputs)

750VA, 500W

1000VA, 670W
1400VA, 950W

Power Factor

500VA, 0.64

750-1400VA, 0.67

Regulation (Normal mode)

-10% to +6% of nominal voltage

Regulation (Battery mode)

240V +5%

Voltage Waveform

Sine wave

Overcurrent Protection

Inverter saturation current limited

Output Receptacles

3 x 10A, Australian

Table 5. Environmental and Safety

Operating Temperature

Up to 1,500 metres: 0

o

C to 40

o

C

Over 1,500 metres: 0

o

C to 35

0

C

Transit/Storage Temperature

-15

o

C to 55

o

C

Relative Humidity

5-95% noncondensing

Operating Altitude

Up to 3,000 metres above sea level

Audible Noise

Less than 45 dBA typical

Surge Suppression

AS/NZS 61000.4.5 1999 Level 3

Safety Conformance

EN 50091-1-1 and IEC 60950

EMC (Class B)

AS62040.2.2001