Model 200erv, Options, Dimensions 200erv – Lifebreath 95MAX User Manual

Page 11: Performance, Engineering data

Advertising
background image

11

OPTIONS

99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)
99-105 Deluxe Programmable Control includes

Programmable Time Clock, Dehumidistat and Air Sentry™

99-109 Air Sentry™ Air Quality Monitor designed to accept remotely

mounted Control Pad

99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh

screen

WARRANTY
Units carry a 5 year warranty on the energy recovery core and
replacement parts.
ERVs are not recommended for regions where the design
temperature is below 25°F (-4°C)

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

14

3

/

4

"

(375)

19"

(483)

*

All Duct Connections 6"(150mm)

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

MOTOR

ALUMINUM CORE

31"

(787mm)

BALANCING

DAMPER

BALANCING

DAMPER

Air Flo

w

(cfm)

200ERV FANCURVE

225

200

175

150

125

100

75

50

25

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Static Pressure (in H2O)

0.8

0.9

1

High

Speed

Low

Speed

Model 200ERV

All units conform to
CSA and UL standards.

DIMENSIONS 200ERV

inches (mm

)

TI-98E

1203

PERFORMANCE

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

232

(109)

@ 0.2” (50 Pa)

223

(105)

@ 0.3” (75 Pa)

215

(102)

@ 0.4” (100 Pa)

195

(92)

@ 0.5” (125 Pa)

189

(89)

Sensible Effectiveness
@ 127 cfm (60 L/s)

(CSA C439M)

67%

Sensible Efficiency 32°F (0

O

C)

60%

Total Efficiency

55%

VAC @ 60HZ

164

WATTS / Low speed

87

ENGINEERING DATA

LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water
vapour between the two airstreams. It is easily removed for cleaning
or service.

MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common
PSC motor. 5 speed fan operation. High speed - 120 VAC.

FILTERS
Washable air filters in exhaust and supply air streams.

MOUNTING THE ERV

Four threaded inserts at corners of case designed to accept four
PVC reinforced polyester straps that are supplied with the unit.

CASE
Twenty gauge prepainted galvanized steel (G60) for superior corro-
sion resistance. Insulated to prevent exterior condensation.

CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode,
Recirculation mode, (each mode has 5 speeds). Control pad can be
removed from HRV and remotely mounted.

WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 65 lbs. (29.6 kg)

511 McCormick Blvd.

270 Regency Ridge,

Suite 210

London, Ontario N5W 4C8

Dayton, Ohio 45459

T (519) 457-1904

T (937) 439-6676

F (519) 457-1676

F (937) 439-6685

Email: [email protected] Website: www.lifebreath.com