Erv questions & answers – Lifebreath 95MAX User Manual

Page 3

Advertising
background image

3

ERV Questions &
Answers

What is the difference between an HRV
and an ERV?

The core in an HRV (Heat Recovery Ventilator)
transfers heat from one air stream to the other. This is
called sensible heat. The term ERV (Energy Recovery
Ventilator) is usually used to describe a unit with an
enthalpic core that transfers moisture as well as heat
from one air stream to the other. This (moisture
transfer) is called latent heat.

Enthalpic - what does it mean?

Enthalpy is the term used to describe the energy
content of air. This energy is a combination of the
sensible and latent heat. Therefore, a core which
transfers energy is called an enthalpic core.

Is an ERV better than an HRV?

NOT NECESSARILY!! In cold climates such as most
of North America, an HRV works better than an ERV.
This is because the air inside the home during the
winter months will be more humid than the outside air.
An ERV would transfer the latent heat (humidity) from
the exhaust air back into the incoming airstream. This
will aggravate moisture problems in the home and
encourage the growth of mold and mildew. If the air in
the home is too dry for comfort, an ERV will not help. A
humidifier should be used to increase the humidity to a
comfortable level.

Where do you use an ERV instead
of an HRV?

An ERV is recommended for warm, humid areas with
heavy air conditioning use. As there is no defrost in an
ERV it is not recommended for areas where the
temperature drops below -4

˚

C (25

˚

F).

Why transfer moisture in the summer
(cooling season)?

The enthalpic core will allow moisture to be transferred
from a humid air flow to a dry air flow. This property is
useful in the cooling season if an air conditioning sys-
tem is used to lower the indoor humidity. You will then
have dry, cool air in the exhaust of the ERV, and warm
humid air in the supply stream. With these conditions,
the ERV will be able to transfer the
moisture and heat of the supply air to the exhaust air.
In this way, the ERV will supply to the home air which
is cooler and drier than outside. Remember that an
ERV is not a dehumidifier, and on its own will not take
moisture out of the air.

So why use an ERV?

A properly operating air conditioner will not only lower

the temperature in your house, but will also lower the
humidity level. This prevents an uncomfortable cold
and damp situation. In fact, about 2/3 of the energy
used by the air conditioner system is to remove
moisture. Therefore, when ventilating in the summer,
less moisture brought into the home means less work
for the air conditioner, and energy savings for you.

During the winter, an ERV recovers some humidity
from the exhaust air, reducing the need for humidification,
if the required ventilation rate would make the home
too dry.

What's the difference between this type of core
and a rotary type?

Here's a list of characteristics of the fixed plate core.

1. No rotating parts, so maintenance is easy and the

unit lasts a long time.

2. It is very flexible in terms of installation.
3. The core can easily be changed.
4. Because the supply and exhaust air streams are

completely separate, there is very little cross
leakage of any dust or germs.

Can the core become clogged with dust?

Because the surface of the core is a turbulent flow
area, dust sticks to it easily; however, because the
inside of the element is a laminar flow area, virtually no
dust sticks to it.

What is the maintenance?

About once a year you should use a vacuum cleaner
to remove the dust from the core's surface. DO NOT
WASH WITH WATER!!

Is an air filter needed?

To prevent clogging of the core, an air filter should
always be installed on the supply and exhaust sides of
the core.

How much ventilation do I need?

During seasons when your windows and doors are
closed, the ERV should operate continuously when
the dwelling is occupied, and either continuously or
intermittently when not occupied.

For most installations the ERV will normally be set to
operate continuously on low speed with the option of
going to high speed as the need arises. For example;
if you are entertaining and there is a large number of
people present (some may be smoking), the unit
should be switched to high speed.

Your ERV may be equipped with automatic or manual
switches, but all ERVs will have a manual speed
control override.