DIRECT CONNECTION of the SUPPLY AIR STREAM to the AIR HANDLER COLD AIR RETURN

(Stale air drawn from key areas of home)

Air

Handler

Outdoors

*Unit is normally balanced on HIGH speed
with air handler blower ON.

High efficiency filter
or electronic air cleaner

Cool Air

Return

NOTES:

1. Air handler blower may be required to operate when HRV is on to provide good air distribution.
2. Weather hood arrangement is for drawing purposes only. 6' (2m) minimum separation required.
18" (460mm) above grade minimum or above anticipated snow level .
3. Due to the differences in pressure between the HRV and the equipment it is being
connected to, the HRV air flow must be confirmed on site, using the balancing
procedure found in the installation manual.

Return Air

3’ min.

recommended

Defrost air port needs to be drawn from clean
area without combustion appliances. To avoid
backdrafting of combustion products, never
draw defrost air from a room with a naturally
aspirated appliance, i.e. furnace, hot water
heater, gas dryer, stove, fire place etc.

WARNING

Weather hood arrangement - requires a minimum
of 6' (2m) separation and a minimum of 18" (460mm)
clearance above grade or anticipated snow level.

CAUTION

Stale air drawn from key areas of

home (bathroom, kitchen, laundry)

Fresh air supplied to return

air duct of air handler

Partially Dedicated System for HRV

HRV must be balanced.

WARNING

Fresh Air From Outside

Field-supplied
Balancing Damper
(optional)

STALE AIR from various parts of home.
i.e. bathrooms (if required), kitchens (if required).

Fresh Air to Building

Exhaust Air to Outside

Application Illustrations

HRV–Option 2