Warning, Caution – Lifebreath RNC120F User Manual

Page 16

Advertising
background image

16

Outdoors

*Unit is normally balanced on HIGH speed
with air handler blower ON.

NOTES:

1. Weather hood arrangement is for drawing purposes only. 6' (2m) minimum separation required.
18" (460mm) above grade minimum or above anticipated snow level .
2. The HRV air flow must be confirmed on site, using the balancing procedure found in the installation manual.

Defrost air port needs to be drawn from clean
area without combustion appliances. To avoid
backdrafting of combustion products, never
draw defrost air from a room with a naturally
aspirated appliance, i.e. furnace, hot water
heater, gas dryer, stove, fire place etc.

WARNING

Weather hood arrangement - requires a minimum
of 6' (2m) separation and a minimum of 18" (460mm)
clearance above grade or anticipated snow level.

CAUTION

Stale air drawn from key areas of

home (bathroom, kitchen, laundry)

Fresh air supplied to main living

areas of home

Fully Dedicated System for HRV

HRV must be balanced.

WARNING

Exhaust Air To Outside

Fresh Air From Outside

Fresh air to house -
main living areas...
bedrooms, living room,
rec. room etc.

Field-supplied Balancing Damper (optional)

STALE AIR from
various parts of home.
i.e. bathrooms
(if required),
kitchens
(if required).

Application Illustrations

HRV–Option 2

Advertising