PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

232

(109)

@ 0.2” (50 Pa)

223

(105)

@ 0.3” (75 Pa)

215

(102)

@ 0.4” (100 Pa)

195

(92)

@ 0.5” (125 Pa)

189

(89)

Maximum Temperature Recovery

81%

Sensible Effectiveness
@ 117 cfm (55 L/s)

(CSA C439M)

74%

Sensible Efficiency
@ 117 cfm (55 L/s) 32˚F (0˚C)

65%

Sensible Efficiency
@ 117 cfm (55 L/s) -13˚F (-25˚C) 66%

VAC @ 60HZ

120

WATTS / Low speed

87

WATTS / High speed

164

Amp rating

1.4

Model 200MAX

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

- Each air stream has one centrifugal

blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.

FILTERS

- Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV

- Four threaded inserts at corners of case

designed to accept four reinforced polyester straps that are
supplied with the unit.

DEFROST

- Recirculating damper defrost system.

DEHUMIDISTAT

- Adjustable Internal Dehumidistat.

CASE

- Twenty gauge prepainted galvanized steel (G60) for superior

corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS

- ControlAir 15

WEIGHT

71 lbs. (32.5 kg

SHIPPING WEIGHT

73 lbs. (33.5 kg)

32 5/8"

(828)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19"

(483)

*All Duct Connections 6" (150mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

DIMENSIONS 200MAX

inches (mm)

OPTIONS

99-104

Digital Electronic Timer

- 20/40/60 min.

99-105

Programmable Ventilation Control

(PVC)

includes Programmable Time Clock, Dehumidistat

and Air Sentry™

99-109

Air Sentry

™ Air Quality Monitor designed to accept

remotely mounted Control Pad

99-250

Ventilation Dehumidistat -

Dehumidistat designed to

accept remotely mounted Control Pad.

99-163

Duct Heater

w/ Electronic SCR Thermostat, 1 Kw,

6” (150mm)

99-164

Duct Heater

w/ Electronic SCR Thermostat, 2 Kw,

6” (150mm)

99-186

Weatherhoods

, Two - 6” (150mm)

c/w 1/4” (6mm) mesh screen

All units conform to CSA and UL standards.

WARRANTY

Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.

TI-99-NE

0103

DATE: __________________________

PROJECT: __________________________________________

MECHANICAL CONTRACTOR: _____________________________

511 McCormick Blvd.

London, Ontario

N5W 4C8

Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
Website: www.lifebreath.com

Advertising
This manual is related to the following products: