Model MAXTOP

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

- Each air stream has one centrifugal

blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.

FILTERS

- Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV

- Four threaded inserts at corners of case

designed to accept four reinforced polyester straps that are supplied
with the unit.

DEFROST

- Recirculating damper defrost system.

DEHUMIDISTAT

- Adjustable Internal Dehumidistat.

CASE

- Twenty gauge prepainted galvanized steel (G60) for superior

corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS

- ControlAir 15

WEIGHT

87 lbs. (39.5 kg)

SHIPPING WEIGHT

89 lbs. (40.5 kg)

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

196

(93)

@ 0.2” (50 Pa)

188

(89)

@ 0.3” (75 Pa)

178

(84)

@ 0.4” (100 Pa)

165

(78)

@ 0.5” (125 Pa)

149

(71)

Maximum Temperature Recovery

80%

Sensible Effectiveness
@ 117 cfm (55 L/s )

(CSA C439M)

72%

Sensible Efficiency
@ 117 cfm (55 L/s) 32

O

F (0°C)

64%

Sensible Efficiency
@ 67 cfm (31 L/s) -13

O

F (-25°C)

70%

VAC @ 60HZ

120

WATTS / Low speed

74

WATTS / High speed

164

Amp rating

1.4

TOP VIEW

SIDE VIEW

25 1/2 "

(648 mm)

26 1/2"

(673 mm)

22 1/2"

(572 mm)

FRONT VIEW

ALL DUCT CONNECTIONS
ARE 6" (150 mm)

18"

(457 mm)

7 1/2"

(191 mm)

SUPPLY OF
FRESH AIR

FRESH AIR
SUPPLY
TO BUILDING

STALE AIR
RETURN FROM
BUILDING

STALE AIR
EXHAUST

DRAIN
CONNECTION

CONTROLS

*Service Clearance
25" (635 mm)

¤

DIMENSIONS MAXTOP

inches (mm)

OPTIONS

99-104

Digital Electronic Timer

- 20/40/60 min.

99-105

Programmable Ventilation Control

(PVC)

includes Programmable Time Clock, Dehumidistat

and Air Sentry™

99-109

Air Sentry

™ Air Quality Monitor designed to

accept remotely mounted Control Pad

99-250

Ventilation Dehumidistat -

Dehumidistat designed

to accept remotely mounted Control Pad

99-163

Duct Heater

w/ Electronic SCR Thermostat, 1 Kw,

6” (150mm)

99-164

Duct Heater

w/ Electronic SCR Thermostat, 2 Kw,

6” (150mm)

99-186

Weatherhoods

, Two - 6” (150mm)

c/w 1/4” (6mm) mesh screen

All units conform to CSA and UL standards.

WARRANTY

Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.

TI-100-NE

0103

DATE: __________________________

PROJECT: __________________________________________

MECHANICAL CONTRACTOR: _____________________________

511 McCormick Blvd.

London, Ontario

N5W 4C8

Ph: (519) 457-1904
Fx: (519) 457-1676