Model 200max rx, Performance, Engineering data – Lifebreath MAXTOP User Manual

Page 10: Dimensions 200max rx

Advertising
background image

10

14 3/4"

(375)

19" (483)

*All Duct Connections 6" (150mm)

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

BALANCING DAMPER

33 5/8"

(850mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

CONDENSATE DRAINS

FILTERS

BLOWERS

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.

All units conform to
CSA and UL standards.

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC
motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40
Recirculation mode, Recirculation mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.

Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)

1105

Model 200MAX RX

DIMENSIONS 200MAX RX

inches (mm)

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

Performance

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

207 (97)

@ 0.2" (50 Pa)

200 (94)

@ 0.3" (75 Pa)

184 (87)

@ 0.4" (100 Pa)

171 (80)

@ 0.5" (125 Pa)

152 (71)

@ 0.6" (150 Pa)

130 (61)

@ 0.7" (175 Pa)

116 (55)

@ 0.8" (200 Pa)

86 (40)

Max. Temperature Recovery

74%

Sensible Effectiveness
@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency
@ 66 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency
@ 109 cfm (51 L/s)

-13°F (-25°C)

62%

VAC @ 60HZ

120

WATTS / Low speed.

87

WATTS / High speed

164

Amp rating

1.4

1

2

3

4

5

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

A

ir

Fl

ow

(

c

fm

)

5 - High Speed
4 - Medium High Speed
3 - Medium Speed
2 - Medium Low Speed
1 - Low speed

Advertising
This manual is related to the following products: