Model 200max, Performance, Dimensions 200max – Lifebreath MAXTOP User Manual

Page 9: Engineering data

Advertising
background image

9

BALANCING DAMPER

33 5/8"

(850 mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375 mm)

19"

(483

mm)

*All Duct Connections 6" (150 mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front
clearance
of 25 inches
(635 mm)
is recommended
for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept

remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to

accept remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”

(150mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”

(150mm)

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh

screen

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.

TI-99-NE

0107

Model 200MAX

DIMENSIONS 200MAX

inches (mm)

All units conform to
CSA and UL standards.

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40
Recirculation mode, Recirculation mode (each mode has 5 speeds). Control
pad can be removed from HRV and remotely mounted.

Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs

Performance

(HVI certified)

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

207 (97)

@ 0.2" (50 Pa)

200 (94)

@ 0.3" (75 Pa)

184 (87)

@ 0.4" (100 Pa)

171 (80)

@ 0.5" (125 Pa)

152 (71)

@ 0.6" (150 Pa)

130 (61)

@ 0.7" (175 Pa)

116 (55)

@ 0.8" (200 Pa)

86 (40)

Max. Temperature Recovery

74%

Sensible Effectiveness
@ 66 cfm (31 L/s)

32°F (0°C)

74%

*Sensible Efficiency
@ 66 cfm (31 L/s)

32°F (0°C)

64%

*Sensible Efficiency
@ 109 cfm (51 L/s)

-13°F (-25°C)

62%

VAC @ 60HZ

120

WATTS / Low speed.

87

WATTS / High speed

164

Amp rating

1.4

1

2

3

4

5

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in w.g.)

A

ir

Fl

ow

(

c

fm

)

5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data

Advertising