18(86) technical data, Table 4-2. technical data – Nx Networks NX series User Manual

Page 18

Advertising
background image

18(86)

Technical data

4

Table 4-2. Technical data

Immunity

Safety

Analogue input voltage

Analogue input current
Digital inputs (6)
Auxiliary voltage
Output reference voltage
Analogue output

Digital outputs

Overcurrent protection

Overvoltage protection
Undervoltage protection

Mains supervision
Motor phase supervision
Unit overtemperature
protection
Motor overload
protection
Motor stall protection
Motor underload
protection
Short-circuit protection
of +24V and +10V
reference voltages

NX_2: 437V; NX_5: 911V; NX_6: 1200V (all VDC)
NX_2: 183V; NX_5: 333V; NX_6: 461V (all VDC)

EMC

Emissions

+24V, ±15%, max. 250mA

Relay outputs

Control
connections

Trip limit 4.0 * I

H

instantaneously

+10 V, +3 %, max. load 10 mA

0...+10V, Ri = 200k

, (–10V...+10V joystick control)

Resolution 0.1%, accuracy ±1%

EMC level H: EN50082-2, EN61800-3 (1st environment,
restricted use; 2nd environment)

Fulfil all EMC immunity requirements

EN50178, EN60204-1, CE, UL, cUL, FI,
GOST R , IEC 61800-5
(see unit nameplate for more detailed approvals)

0(4)…20mA; R

L

max 500

, Resolution 10 bit, Accur. ±2%

Open collector output, 50mA/48V
2 programmable change over relay outputs
Max. switching voltage 125Vdc/250Vac
Max. switching current 6A/24Vdc, 0.4A/250 Vac
Max. continuous current 2 A rms

0(4)…20mA, R

i

= 250

differential

Positive or negative logic; 18…24 Vdc

Yes

Yes

Protections

Trips if any of the output phases is missing
Yes

Yes

Yes

In case of earth fault in motor or motor cable, only
the frequency converter is protected

Earth-fault protection

Trips if any of the input phases is missing