7.3.4.2 Fault

codes

The fault codes, their causes and corrective actions are presented in the table below. The
shadowed faults are A faults only. The faults written in white on black background may appear as
both A and F fault.

Fault
code

Fault

Possible cause

Correcting measures

1

Overcurrent

Frequency converter has detected too
high a current (>4*I

n

) in the motor cable:

sudden heavy load increase

short circuit in motor cables

unsuitable

motor

Check loading.
Check motor.
Check cables.

2

Overvoltage

The DC-link voltage has exceeded the
limits defined in Table 4-1.

too short a deceleration time

high overvoltage spikes in supply

Make the deceleration time longer. Use
brake chopper or brake resistor
(available as options)

3

Earth fault

Current measurement has detected that
the sum of motor phase current is not
zero.

insulation failure in cables or motor

Check motor cables and motor.

5

Charging switch

The charging switch is open, when the
START command has been given.

faulty

operation

component

failure

Reset the fault

and restart.

Should the fault re-occur, contact your
nearest distributor..

6

Emergency

stop

Stop signal has been given from the
option board.

7

Saturation trip

Very high overload
Defective component

Cannot be reset from the keypad.
Switch off power. If this does not help
contact your nearest distributor.

8

System fault

The frequency converter troubleshooting
system is unable to locate the fault.

Reset the fault

and restart.

Should the fault re-occur, contact your
nearest distributor.

9

Undervoltage

DC-link voltage is under the voltage limits
defined in.

most probable cause: too low a
supply voltage

frequency converter internal fault

In case of temporary supply voltage

break reset the fault

and restart

the frequency converter. Check the
supply voltage. If it is adequate, an
internal failure has occurred.
Contact your nearest distributor.

10

Input line
supervision

Input line phase is missing.

Check supply voltage and cable.

11

Output phase
supervision

Current measurement has detected that
there is no current in one motor phase.

Check motor cable and motor.

12

Brake chopper
supervision

no brake resistor installed

brake resistor is broken

brake chopper failure

Check brake resistor.
If the resistor is ok, the chopper is faulty.
Contact your nearest distributor..

13

Frequency
converter under-
temperature

Heatsink temperature is under –10

°

C

14

Frequency
converter over
temperature

Heatsink temperature is over 90

°

C.

Over temperature warning is issued when
the heatsink temperature exceeds 85

°

C.

Check the correct amount and flow of
cooling air.
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load.

15

Motor stalled

Motor stall protection has tripped.

Check motor.