34(86) cabling and connections, 1 stripping lengths of motor and mains cables – Nx Networks NX series User Manual

Page 34

Advertising
background image

34(86)

Cabling and connections

6

6.1.2.1 Stripping lengths of motor and mains cables

Figure 6-3. Stripping of cables

Frame

A1

B1

C1

D1

A2

B2

C2

D2

FR4

15

35

10

20

7

50

7

35

FR5

20

40

10

30

20

60

10

40

FR6

20

90

15

60

20

90

15

60

FR7

25

120

25

120

25

120

25

120

FR8

0140

0168—0205

23
28

240
240

23
28

240
240

23
28

240
240

23
28

240
240

Table 6-3. Cables stripping lengths [mm]

nk6141.fh8

MAINS

MOTOR

Earth

conductor

Earth

conductor

D1

B1

C1

A1

D2

B2

C2

A2

Advertising